Accuracy
- Clock: ± 100 ppm or Less
- Digital Indication (K Thermocouple): ± (0.3 % + 1-Digit)
- Digital Indication (Ni100, Cu50 Resistance Bulb): ± (0.5 % + 1-Digit)
- Digital Indication (R Thermocouple, JPt100, Pt100, Pt50 Resistance Bulb, DC Voltage): ± (0.15 % + 1-Digit)
Ambient Temperature Range
- With Ethernet Function: 0° to 40° C (32° to 104° F)
- Without Ethernet Function: 0° to 50° C (32° to 122° F)
Approvals & Certifications
Communication
- Baud Rate: 9,600, 19,200 bit/sec
- EIA RS-485
- Ethernet
- FTP
- HTTP
- Modbus RTU
- Modbus TCP/IP
- RS-232C
- SMTP (E-mail Client)
Consumption
- Power: 36 VA at 100 Vac
- Power: 47 VA at 240 Vac
Electrical Connectors
- D-Sub Terminal
- M3 Screw Terminal
- RJ45 (Ethernet Terminal)
Electrical Rating
- Alarm Output: 100 mA at 30 Vdc - Resistive Load
- Alarm Relay: 3 A at 150 Vac / 240 Vac (Resistive Load)
- Alarm Relay: 3 A at 30 Vdc
Environmental Protection
- IP20 (Terminal)
- IP50 (Front)
Frequency
- Effect of Power Supply Fluctuation Conditions: 47 to 63 Hz [Reading Change (100 Vac & 50 Hz Base): ± (0.2 % + 1-Digit) or Lower]
- Power Supply, Normal Operating Condition (± 2 %): 50/60 Hz (Both Employable)
Function
- Burn-Out
- F Value Calculation
- Input Filter
- Mathematics
- Scaling
- Square Rooter
- Subtraction
- Totalization
Humidity
- Ambient: 20 to 80 % Relative Humidity
- Transportation/Storage Conditions: 5 to 90 % Relative Humidity, Non-Condensing
Hysteresis
- Alarm Function: 0 to 100 %
Indication
- 5.7” TFT Color LCD (320 x 240 Dots) with Backlight, No Contrast Adjustment
Input
- 0-5 Vdc
- DC Voltage: 0-500 mV
- Resistance Bulb Measured Current: 1 mA
- Thermocouple, Resistance Bulb, DC Voltage: ± 10 Vdc (Continuous) - Max.
Insulation Resistance
- 100 megaohms or more (When Measured between Each Terminal & Ground by Using A 500 Vdc Megger)
Measuring Range
- Resistance Bulb: -200° to 600° C (-328° to 1,112° F)
- Thermocouple: -200° to 1,760° C (-328° to 3,200° F)
Mounting
- Panel-Mounted (Vertical Panel)
Mounting Position
- Backward Tilt within 30° Slant [Reading Change: ± (0.2 % + 1-Digit) or Lower]
- Mounting Posture (Forward Tilt & Horizontal): 0°
Pulse Range
- DI Input Pulse Width (ON/OFF): 200 milliseconds or Longer
Resistance
- Input (Thermocouple, DC Voltage): 1 Megaohm
- Signal Source Resistance (Resistance Bulb Input): 10 ohms/Wire or Less [Reading Change: ± (0.2 % + 1-Digit) or Lower
- Signal Source Resistance (Thermocouple Input): 1 Kiloohm or Less
Resistance Effect
- Effect of Input Signal Resistance: (0.5 µV/ohms) + 1-Digit or Less
Resolution
- Digital Indication (0-5 Vdc & 1-5 Vdc): 1 mV
- Digital Indication (50 mVdc Voltage): 10 µV
- Digital Indication (500 mVdc Voltage): 100 µV
- Digital Indication: 0.1° C (0.18° F) for Thermocouple & Resistance Bulb
Sensor, Probe Type
- B Thermocouple
- E Thermocouple
- J Thermocouple
- K Thermocouple
- L Thermocouple
- N Thermocouple
- PN Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
- U Thermocouple
- W Thermocouple
Shock
- Transportation/Storage Conditions: 294 m/sec² or Lower (Packed State)
Storage Temperature
- -10° to 60° C (14° to 140° F)
System Requirements
- Windows® 2000/7/XP (Home Premium, Professional (Not Applicable for 64-bit Version)
Temperature Effect
- Ambient (Reading Change): ± (0.3 % + 1-Digit)/10° C or Lower
Temperature Range
- Transportation: -10° to 60° C (14° to 140° F)
Time Constant
- Input Filter Function: 0 to 900 seconds
Vibration
- Normal Operating Condition: 10-60 Hz, 0.2 m/sec² or Less
- Transportation/Storage Conditions: 10-60 Hz, 2.45 m/sec² or Lower
Voltage
- Withstand Voltage [Alarm Terminal - Alarm Terminal]: 750 Vac, 1 Minute
- Withstand Voltage [Input Terminal - Ground, Communication Terminal - Ground, Alarm Terminal (Open Collector) - Ground]: 500 Vac, 1 Minute
- Withstand Voltage [Power Terminal - Ground, Alarm Terminal - Ground]: 2,000 Vac, 1 Minute