Accuracy
- Cooling, Auxiliary Analog (Re-Transmission) Input/Output: ± 0.2 % of Full Scale
- Detected Current Accuracy: Setting ± 10 % of Full Scale
- Input Indication: ± 0.1 % of Full Scale
- Resistance Bulb Input: (± 0.1 % of Full Scale ± 1-Digit) or ± 0.25° C (0.45° F), whichever is Larger
- Thermocouple B (0° to 400° C): ± 5 % of Full Scale ± 1-Digit ± 1° C (± 1.8° F)
- Thermocouple R (0° to 500° C Range): ± 1 % of Full Scale ± 1-Digit ± 1° C ± 1° C (± 1.8° F)
- Thermocouple: ± 0.1 % of Full Scale ± 1-Digit ± 1° C (± 1.8° F) or ± 1.5° C (± 2.7° F), whichever is Larger
- Voltage, Current Input: ± 0.1 % of Full Scale ± 1-Digit
Ambient Temperature Range
- -10° to 50° C (14° to 122° F)
Approvals & Certifications
Communication
- Baud Rate: 9,600, 19,200, 38,400 bit/sec
- Data Length: 8-bits, Parity, Odd / Even / None
- Method: 3-Wire, Half-Duplex Bit Serial
- Method: Asynchronous Communication
- PC Loader Interface: RS-232C
- Protocol: Modbus RTU
- RS-485
Connectors
- PC Loader Interface: Miniature Jack on Bottom Face
Consumption
- Power Consumption: 15 VA or Less (100 Vac)
- Power Consumption: 20 VA or Less (220 Vac)
Control Functions Characteristics
Distance
- RS-485 Communication Distance: 0 to 1,640 feet (0 to 500 metres)
Electrical Rating
- 3-Digital Input: 2 mA at 12 Vdc
- Contact Capacity: 3 A at 30 Vdc
- Cooling / Motorized Valve Operation Pulse Output: 0.3 A at 220 Vac / 30 Vdc
- Relay Contact / Digital / Cooling / Motorized Valve Operation Pulse Output: 1 A at 220 Vac / 30 Vdc (Inductive Load)
- Relay Contact: 3 A at 220 Vac / 30 Vdc - Resistive Load
Enclosure, Body Material
- Plastic (Flame-Resistant, UL 94V-0)
Environmental Protection
- Body: IEC IP20 (Provided with Slits on Top & Bottom Faces)
- Front Face: IP66 (When Mounted on Panel with Our Genuine Packing. Waterproof Feature Unavailable in Side-by-Side Mounting)
- Front Face: NEMA 4X (When Mounted on Panel with Our Genuine Packing. Waterproof Feature Unavailable in Side-by-Side Mounting)
- Terminal Section: IEC IP00 (Terminal Cover Can be Mounted)
Filter
- First Order Lag Filter: 0 to 900 seconds
Function
- Alarm (Heater Burn-Out) Detectable Range: 1-50 A, Detected Current / Setting Resolution: 0.1 A
Humidity
- Operating/Storage Ambient Humidity: 90 % Relative Humidity, Max.
Input
- Current Input: -25 to 25 mA
- DC Voltage Input: -10 to 35 V
- Heater Current Detector (CT): 1-30 A
- Heater Current Detector (CT): 20-50 A
- Input Judgment: OFF Assumed at 100 kiloohms or Higher (Contact) or 18 Vdc or Higher (Transistor)
- Input Judgment: ON Assumed at 1 Kiloohm or Lower (Contact) or 5 Vdc or Lower (Transistor)
- Thermocouple, Resistance Bulb, mV Input: 0-10 Vdc
- Thermocouple, Resistance Bulb, mV Input: 0-20 mVdc
- Thermocouple, Resistance Bulb, mV Input: 0-5 mV
- Thermocouple, Resistance Bulb, mV Input: 4-20 mA DC
Input Impedance
- Process Value Input: 250 ohms
- Thermocouple, mV, Voltage & Auxiliary Analog (Remote SV) Input: 1 Megaohm Min.
Input Signal
- 0-50 mV
- Auxiliary Analog Input (Remote SV Input): 0-5 Vdc
Linearity
- Current Output: ± 0.2 % of Full Scale
Load Resistance
- SSR/SSC Drive Output: 850 ohms Min.
- SSR / SSC Drive / Auxiliary Analog (Re-Transmission) Output (Current): 600 ohms or more or Less
- SSR/SSC Drive/Auxiliary Analog (Re-Transmission) Output (Voltage): 10 kiloohms Min.
Operation
- Contact Life (Output): 100,000 times or more (Rated Load)
Output
- Auxiliary Analog (Re-Transmission) Output: 0-10 Vdc
- Auxiliary Analog (Re-Transmission) Output: 0-20 mA
- Auxiliary Analog (Re-Transmission) Output: 0-5 Vdc
- Auxiliary Analog (Re-Transmission) Output: 1-5 Vdc
- Auxiliary Analog (Re-Transmission) Output: 4-20 mA
- SSR/SSC Drive Output (ON): 20 Vdc (18-24 Vdc)
- Transmitter Power Supply Output: 23 mA
- Transmitter Power Supply Output: 24 Vdc (17-30 Vdc)
Output Noise
- Noise Rejection Ratio (Common Mode): 120 dB (50/60 Hz)
- Noise Rejection Ratio (Normal Mode): 40 dB (50/60 Hz)
Power Supply
- 100-240 Vac (-15 %, 10 %), 50/60 Hz
Resistance
- Input: 250 ohms
- Resistance Bulb: 10 ohms or Less (per Cable)
- Valve Opening Feedback Signal (Potentiometer): 100 to 10,000 ohms, 3-Wire
- Variation by Signal Source Resistance: Thermocouple, mV Input ± 0.3 % of Full Scale ± 1-Digit Per 100 ohms
- Variation by Signal Source Resistance: Voltage Input ± 0.3 % of Full Scale ± 1-Digit Per 500 ohms
Resistance Effect
- Auxiliary Analog Input: 0.2 % of Full Scale Per 500 ohms
- Thermocouple, Voltage Input (mV): 0.1 % of Full Scale Per 100 ohms
- Voltage Input (V): 0.1 % of Full Scale Per 500 ohms
Resolution
- Resistance Bulb Input: 0.01° C
- Valve Opening Feedback Signal (Potentiometer): ± 0.1 % of Full Scale
RTD Type
- Resistance Bulb: Pt100 ohms (3-Wire)
Sample Rate
- Auxiliary Analog Input: 100 milliseconds
- Input Control Cycle: 50 milliseconds
Sensor, Probe Type
- B Thermocouple
- E Thermocouple
- J Thermocouple
- K Thermocouple
- N Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
Storage Temperature
- -20° to 60° C (-4° to 140° F)
Supply Voltage
- Withstand Voltage: 500 Vac for 1 Minute
- Withstand Voltage: Power Source to All Terminals, Relay Contact Output to All Terminals 1,500 Vac for 1 Minute
Switch Type
- Motorized Valve Operation Pulse / Cooling / Digital Output: SPDT
- Relay Contact / Digital Output: SPDT
Temperature Range
- -200° to 2,300° C (-328° to 4,172° F)
Terminal Strip
- External Terminal: M3 Screw Terminal