  • Product Type: Large Display NEMA 4X High Voltage & Current Meter
  • Inputs: (Two, One Each), High Voltage (0-300 V), High Current (0-5 A)
  • Outputs: 4 Relays & 4-20 mA Output
  • Power: 12-24 VDC/VAC
  • Transmitter Power: 24 VDC @ 40 mA
  • Display: SunBright, 1.8", Dual Line, 6 Digits, Red LED
  • Serial Communications: RS-485 Modbus
  • Approvals: UL/C-UL
  • Warranty: 3 years

Specifications

Display

  • Two lines with 1.8” (46 mm) High Digits, Red LEDs, 6 Digits per line (-99999 to 999999), with Lead Zero Blanking

Display Intensity

  • Eight user-selectable intensity levels

Display Update Rate

  • 5/second (200 ms)

Overrange

  • Display flashes 999999

Underrange

  • Display flashes -99999

Display Assignment

  • Displays lines 1 & 2 may be assigned to process values for Channels A (Ch-A, Current), V (Ch-V, Voltage), or P (Ch-P, apparent Power), toggle between (Ch-A & Ch-V, Ch-A & Ch-P, Ch-V & Ch-P, and Ch-A, Ch-V, & Ch-P), Relay Set Points, max and/or min values for CH-A, Ch-V, or Ch-P, CH-A and units, Ch-V and units, Ch-P and units, or Modbus Input. The Lower display may also be set to show engineering units or be off, with no display.

Noise Filter

  • Programmable from 2 to 199 (0 will disable filter)

Filter Bypass

  • Programmable from 0.1 to 99.9 % of Calibrated Span

Recalibration

  • All Ranges are calibrated at the factory. Recalibration is recommended at Least every 12 months.

Maximum / Minimum Display

  • Max./Min. Readings reached by the process are stored until reset by the user or until power to the meter is turned off.

Passwords Restrict Modification

  • Pass 1: Allows use of function keys and digital inputs
  • Pass 2: Allows use of function keys, digital inputs and editing set/ reset Points
  • Pass 3: Restricts all Programming, function keys, and digital inputs

Non-Volatile Memory

  • All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.

Power Options

  • 85-265 Vac 50/60 Hz, 90-265 Vdc, 20 W max
  • 12-24 Vdc ± 10 %, 15 W Max. Powered over USB for configuration only.

Fuse

  • Required External Fuse: UL Recognized, 5 A max., Slow Blow, up to 6 metres may share one 5 A fuse

Normal Mode Rejection

  • Greater than 60 dB at 50/60 Hz

Isolation

  • 500 Vac/dc potential Allowed between Voltage and Current Input channels. Channels isolated by 3 MΩ impedance 4 kV Input/output-to-Power line 500 V Input-to-output or output- to-P+ Supply.

Overvoltage Category

  • Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.

Environmental

  • Storage Temperature Range: -40 to 185° F (-40 to 85° C)
  • Relative Humidity: 0 to 90 % Non-Condensing
  • Operating Temperature Range: -40 to 150° F (-40 to 65° C)

Connections

  • Removable and integrated screw terminal blocks accept 12 to 22 AWG wire.

Enclosure

  • UL Type 4X, IP65 rated. Polycarbonate & glass blended plastic Case, color: gray. Includes four PG11 through-hole conduit openings, with two factory installed PG11, IP68, Black nylon threaded hole plugs with backing nuts.

Wall Mounting

  • Four (4) mounting holes provided for mounting meter to wall

Pipe Mounting

  • Optional Pipe Mounting Kit (PDA6260) Allows for Pipe Mounting. Sold Separately. See manual for Mounting instructions.

Tightening Torque

  • Removable Screw Terminals: 5 lb-in (0.56 Nm)
  • Digital I/O and RS-485 Terminals: 2.2 lb-in (0.25 Nm)

Overall Dimensions

  • 10.63” x 12.59” x 4.77” (270 mm x 319.7 mm x 121.2 mm) (W x H x D)

Weight

  • 6.10 lbs (2.76 kg)

UL File Number

  • UL & C-UL Listed. E160849, 508 Industrial Control Equipment.

Warranty

  • 3 Years Parts & Labor

USB Connection

  • Compatibility: USB 2.0 Standard, Compliant
  • Connector Type: Micro-B receptacle
  • Cable: USB A Male to Micro-B Cable
  • Driver: Microsoft Windows® XP/Vista/7/8/10
  • Power: USB Port
show more