Accuracy
- Clock: ± 50 ppm
- Digital Indication (K Thermocouple): ± (0.3 % + 1-Digit)
- Digital Indication (Ni100, Cu50 Resistance Bulb): ± (0.5 % + 1-Digit)
- Digital Indication (R Thermocouple, JPt100, Pt100, Pt50 Resistance Bulb, DC Voltage): ± (0.15 % + 1-Digit)
Ambient Temperature Range
- With Ethernet Function: 0° to 40° C (32° to 104° F)
- Without Ethernet Function: 0° to 50° C (32° to 122° F)
Approvals & Certifications
Communication
- Ethernet
- FTP
- HTTP
- Modbus TCP/IP
- SMTP (E-mail Client)
Consumption
- Power: 65 VA at 100 Vac
- Power: 80 VA at 240 Vac
Electrical Connectors
- External Terminal Board (Input Terminal): M3 Screw Terminal
- External Terminal Board (Power Terminal): M4 Screw Terminal
Electrical Rating
- Alarm Relay: 3 A at 240 Vac (Resistive Load)
- Alarm Relay: 3 A at 30 Vdc - Resistive Load
- Alarm: 0.1 A at 30 Vdc - Resistive Load
Frequency
- Effect of Power Supply Fluctuation Conditions: 47 to 63 Hz (100 Vac) [Reading Change: ± (0.2 % + 1-Digit) or Lower]
- Power Supply: 50/60 Hz ± 2 % (Both Employable & Sharing)
Function
- Burn-Out
- Computation
- F Value Calculation
- Input Filter
- Scaling
- Square Rooter
- Subtraction
- Totalization
Humidity
- Ambient: 20 to 80 % Relative Humidity
- Transportation/Storage Conditions: 5 to 90 % Relative Humidity
Hysteresis
- Alarm Function: 0 to 100 %
Indication
- 12” TFT Color LCD (800 x 600 Dots) with Backlight, No Contrast Adjustment
Input
- 0-5 Vdc
- DC Voltage: 0-500 mV
- Thermocouple, Resistance Bulb, DC Voltage: ± 10 Vdc (Continuous) - Max.
Input Impedance
- Thermocouple, DC Voltage: 1 Megaohm
Insulation Resistance
- 100 megaohms (When Measured between Each Terminal & Ground by Using A 500 Vdc Megger)
Materials of Construction
Measuring Error
- K, E, J, T, N, L, U, PN Thermocouple: ± 0.5° C (0.9° F)
- R, S, B, W Thermocouple: ± 1° C (1.8° F)
Measuring Range
- Resistance Bulb: -200° to 600° C (-328° to 1,112° F)
- Thermocouple: -200° to 1,760° C (-328° to 3,200° F)
Mounting
- Panel-Mounted (Vertical Panel)
Mounting Position
- Backward 30° Slant [Reading Change: ± (0.2 % + 1-Digit) or Lower]
Power Supply
- 90-264 Vac at 50/60 Hz
- Rated: 100-240 Vac
Pulse Range
- Input Pulse Width (ON/OFF): 400 milliseconds
Resistance
- Signal Source Resistance (Resistance Bulb Input): 10 ohms/Wire or Less [Reading Change: ± (0.2 % + 1-Digit) or Lower]
- Signal Source Resistance (Thermocouple Input): 1 Kiloohm or Less
Resistance Effect
- Effect of Input Signal Resistance (Thermocouple Input): 50 μV ± 1-Digit/100 ohms
Resolution
- Digital Indication: 0.1° C (0.18° F) for Thermocouple & Resistance Bulb
- Digital Indication: 1 mV for 5 Vdc
- Digital Indication: 10 V for 50 mVdc
- Digital Indication: 100 V for 500 mVdc
Sensor, Probe Type
- B Thermocouple
- E Thermocouple
- J Thermocouple
- K Thermocouple
- L Thermocouple
- N Thermocouple
- PN Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
- U Thermocouple
- W Thermocouple
Shock
- Transportation/Storage Conditions: 294 m/sec² or Lower (Packed State)
Storage Temperature
- -10° to 60° C (14° to 140° F)
System Requirements
- Windows® 2000/XP (Windows® Vista is Not Supported)
Temperature Effect
- Ambient (Reading Change): ± (0.3 % + 1-Digit)/10° C or Lower
Temperature Range
- Transportation: -10° to 60° C (14° to 140° F)
Time Constant
- Input Filter Function: 0 to 900 seconds
Vibration
- 10-60 Hz with the Acceleration of 0.2 m/sec² or Less [Reading Change: ± (0.2 % + 1-Digit) or Lower]
- Transportation/Storage Conditions: 10-60 Hz, 2.45 m/sec² or Lower
Voltage
- Withstand Voltage [Alarm Terminal (Contact Output) - Alarm Terminal (Contact Output)]: 750 Vac, 1 Minute
- Withstand Voltage [Input Terminal - Input Terminal, Input Terminal - Ground, Communication Terminal - Ground, Alarm Terminal (Open Collector) - Ground, Power Terminal - Input Terminal]: 500 Vac, 1 Minute
- Withstand Voltage [Power Terminal - Ground, Alarm Terminal (Contact Output) - Ground]: 2,000 Vac, 1 Minute