MIST M340 RTD Temperature Transmitter
Brand: Intempco Controls, IncThe MIST M340 RTD Temperature Transmitter consists of surface mount ring type RTD, extension cable to remote transmitter and M12 connector.
It is designed for heavy duty BTU temperature measurement applications due to its very high accuracy. As all the other MIST Series transducers, it can be re-calibrated and re-scaled in the field.
Features- Output signals: 4-20 mA 2-wire; 0-5, 1-5, 0-10 Vdc 3-wire
- Input: platinum RTD 100, Class A, 3-wire
- Ranges: standard and programmable from 50° to 200° C (-58° to 392° F)
- Power supply: 10-32 Vdc polarity protected
- Accuracy: ±(0.10° C (0.18° F) + 0.10% of calibrated span) with two-point calibration
- Wetted material: stainless steel 316/316L, dual certified
- Housing: stainless steel 316
- Electrical connection: M12 male receptacle
- Operating temperature range: -40° to 80° C (104° to 176° F) (housing only)
- Protection: meets NEMA 6P, IP67 (IEC 529)
Specifications
Accuracy
- ± (0.10° C (0.18° F) + 0.10 % of Calibrated Span) with Two-Point Calibration
- ± (0.25° C (0.45° F) + 0.40 % of Span) with One-Point Calibration
Cable Material
- PVC
- Teflon
Electrical Connectors
- M12 Male Receptacle
Environmental Protection
- IP67 Hermetically Sealed
- NEMA 6P Hermetically Sealed
Input Impedance
- 1,000 ohms Min. (of Measuring Device, for Voltage Output)
Isolation
- 500 Vdc Input/Output
Lead Insulation
- Fiberglass with Stainless Steel Armor & Overbraid
- PVC
- Teflon with Stainless Steel Armor & Overbraid
Mounting
- Surface Mount Solid Plate (1/16" THK Aluminum)
Operating Pressure
- Sensor psig: 500 (kPa: 3,447, bar: 34.47)
Operating Temperature
- Housing: -40° to 80° C (-40° to 175° F)
Output
- 0-10 Vdc Linear to Temperature
- 0-5 Vdc Linear to Temperature
- 1-5 Vdc Linear to Temperature
- 4-20 mA Loop-Powered, Linear to Temperature
Power Supply
- 12-32 Vdc Polariity Protected
Power Supply Effect
- 0.001 %/V
RFI/EMI Effect
- RFI: 1 % or Less Typical
Ring Material
- 316 Stainless Steel
- Aluminum
- Brass
RTD Type
- Pt100
Sensor Circuit
- 2.5 mA Downscale for 4-20 mA Output
- 24 mA Upscale for 4-20 mA Output
Sensor, Probe Connection
- 2-Wire
- 3-Wire
Sensor, Probe Type
- RTD
Stability
- Long Term Drift: ≤ 0.1 % of Full Scale Per Year
Storage Temperature
- -40° to 80° C (-40° to 176° F)
Temperature Effect
- ± 0.001 % of Span/°C
Temperature Range
- -50° to 400° C (-58° to 752° F)
Update Time
- Warm-Up: 30 seconds
Wetted Materials
- 316 Stainless Steel, Dual Certified
- 316L Stainless Steel, Dual Certified