Accuracy
- B Thermocouple: ± 5 % of Measurement Range ± 1-Digit ± 1° C (± 1.8° F) at 0° to 400° C (32° to 752° F)
- Reference Junction Compensation: ± 1° C (± 1.8° F) at 23° C (73.4° F)
- Remote Set Point: ± 0.5 % ± 1-Digit
- Re-transmission Output: ± 0.3 % of Full Scale
- R Thermocouple: ± 1.0 % of Measurement Range ± 1-Digit ± 1° C (± 1.8° F) at 0° to 500° C (32° to 932° F)
- Thermocouple: ± 0.5 % of Measurement Range ± 1-Digit ± 1° C (± 1.8° F)
- Voltage/Current: ± 0.5 % of Measurement Range ± 1-Digit
Ambient Temperature Range
- -10° to 50° C (14° to 122° F)
Approvals & Certifications
- CE: LVD: EN 61010-1, EMC: 1326-1
- CSA: C22.2 No. 24-93
- UL (C): UL 873
Approvals & Certifications
Communication
- Baud Rate: 9,600 bit/sec
- Communication Protal: Modbus RTU with Windows®-based Software PXR-LITE
- Data Length: 8-bits, Parity, Odd / Even / None
- Method: 2-Wire, Half-Duplex Bit Serial
- RS-232, RS-485, RS-232, RS-485 Signal Converter: RSFC24
- RS-485
Consumption
- Power Consumption: 6 VA (100 Vac)
- Power Consumption: 8 VA (220 Vac)
Control Functions Characteristics
- Self-Tuning, Fuzzy, Auto-Tuning: PID Control
Current
- Current Detector: 1-50 A
- SSR: 20 mA or Less
Delay Time
- Alarm ON-Delay: 0 to 9,999 seconds Set 1 second steps
Distance
- Communication Distance: 1,640 feet (500 metres) or Less
Electrical Rating
- Relay Contact: 3 A at 220 Vac / 30 Vdc - Resistive Load
Environmental Protection
- Faceplate: IP66
- Faceplate: NEMA 4X
- Rear Case: IEC IP20
Filter
- 0 to 90 seconds Set in 0.5 second steps
Humidity
- Operating/Storage Ambient Humidity: less than 90 % Relative Humidity, Non-Condensing
Input
- 0-20 mA
- 0-5 V
- 4-20 mA
- Remote Set Point: 1-5 Vdc, 1-Point
Input Impedance
- Remote Set Point: 1 Megaohm or more
Load Resistance
- Control Output (4-20 mA DC): 100 to 500 ohms
Mounting
- DIN Rail Mounting
- Panel Flush Mounting
Output
- Process Alarm: 1 A at 220 Vac / 30 Vdc, Max.
- Re-transmission Output: 4-20 mA DC
- SSR: 12-16 Vdc
Power Supply
- 100 to 240 Vac (-15 %, 10 %), 50/60 Hz
- 24 Vac/dc, 50/60 Hz
Sensor, Probe Type
- B Thermocouple
- E Thermocouple
- J Thermocouple
- K Thermocouple
- N Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
Storage Temperature
- -20° to 60° C (-4° to 140° F)
Terminal Strip
- External Terminal: Screw Terminal Strip