  • Front Panel Size - 1/16 DIN (48 x 48 mm)
  • Input Signal - Thermocouple (° C)
  • Output 1 - Relay Contact Output
  • Alarm Option - Without Alarm Option
  • Power Supply - 100-240 Vac, 50/60 Hz

Specifications

Accuracy

  • B Thermocouple: ± 5 % of Measurement Range ± 1-Digit ± 1° C (± 1.8° F) at 0° to 400° C (32° to 752° F)
  • Input Value Correction: ± 10 % of Measuring Range
  • Reference Junction Compensation: ± 1° C (± 1.8° F) at 23° C (73.4° F)
  • R Thermocouple: ± 1.0 % of Measurement Range ± 1-Digit ± 1° C (± 1.8° F) at 0° to 500° C (32° to 932° F)
  • Set Value Correction: ± 50 % of Measuring Range
  • Thermocouple: ± 0.5 % of Measurement Range ± 1-Digit ± 1° C (± 1.8° F)
  • Voltage/Current: ± 0.5 % of Measurement Range ± 1-Digit

Ambient Temperature Range

  • -10° to 50° C (14° to 122° F)

Consumption

  • Power Consumption: 10 VA or Less (220 V & 24 Vac/dc)
  • Power Consumption: 8 VA (100 V)

Control Functions Characteristics

  • Self-Tuning, Fuzzy, Auto-Tuning: PID Control

Cover Type

  • Terminal Cover

Current

  • Minimum Switching Current: 100 mA (5 Vdc)
  • SSR/SSC Drive: Max.

Delay Time

  • Alarm ON-Delay: 0 to 9,999 seconds Set 1 second steps

Display

  • Large 4-Digit LED

Electrical Rating

  • Relay Contact: 3 A at 220 Vac / 30 Vdc - Resistive Load

Enclosure, Body Material

  • Plastic (Non-Combustible)

Environmental Protection

  • Faceplate: IP66
  • Faceplate: NEMA 4X
  • Rear Case: IEC IP20

Filter

  • Input Filter: 0 to 900 seconds Settable in 0.5 second steps

Humidity

  • Operating/Storage Ambient Humidity: less than 90 % Relative Humidity, Non-Condensing

Input

  • 4-20 mA
  • Remote Set Point: 1-5 Vdc, 1-Point

Input Impedance

  • Current: 250 ohms (External Resistor)
  • Thermocouple: 1 Megaohm or more
  • Voltage: 450 kiloohms or more

Insulation Resistance

  • 20 megaohms or more at 500 Vdc

Load Resistance

  • Output (4-20 mA DC): 600 ohms or Less

Measuring Range

  • -150° to 1,800° C (-238° to 2,912° F)

Mounting

  • DIN Rail Mounting
  • Panel Flush Mounting

Operation

  • Electrical Life (Relay Contact/Digital Output): 100,000 Operations Min.
  • Mechanical Life: 10 Million Operations (No Load)

Output

  • 4-20 mA DC
  • Process Alarm: 1 A at 220 Vac / 30 Vdc, Max.
  • SSR/SSC Drive (OFF): 0.5 Vdc
  • SSR/SSC Drive (ON): 17-25 Vdc

Output Noise

  • Noise Reduction Ratio (Common Mode): 140 dBor more (50/60 Hz)
  • Noise Reduction Ratio (Normal Mode): 50 dB or more (50/60 Hz)

Power Supply

  • 100-240 Vac (-15 %, 10 %), 50/60 Hz
  • 24 Vac/dc (± 10 %), 50/60 Hz

Resistance

  • Allowable Signal Source Resistance (Thermocouple): 100 ohms or Less
  • Allowable Signal Source Resistance (Voltage): 1 Kiloohm or Less
  • Allowable Wiring Resistance (Resistance Bulb): 10 ohms or Less Per Wire

RTD Type

  • Pt100

Sensor, Probe Type

  • B Thermocouple
  • E Thermocouple
  • J Thermocouple
  • K Thermocouple
  • N Thermocouple
  • R Thermocouple
  • S Thermocouple
  • T Thermocouple

Storage Temperature

  • -20° to 60° C (-4° to 140° F)

Supply Voltage

  • Dielectric Strength (Others): 500 Vac/minute
  • Dielectric Strength (Power Supply-Ground, Power Supply-Others, Ground-Relay Output, Ground-Alarm Output): 1,500 Vac/minute

Switch Type

  • SPDT
  • SPST

Termination

  • External Terminal: 8-Pins or 11-Pins Terminals (Socket is Required for Wiring Separately)