  • Control Type - Basic Type
  • Front Panel Size - 96 x 96 mm
  • Control Loop / Function - 1-Loop Basic Controller
  • Input - Universal Input: 1-Point
  • Auxiliary Input - No Fitted
  • Output 1 / Output 2 - Current / No Fitted
  • Power Supply - 100-240 Vac
  • Communication Interface - Without Communication
  • Digital Input / Output - 4-Points (DI1 to DI4) / 2-Points (DO3, DO4)

Specifications

Accuracy

  • Cooling, Auxiliary Analog (Re-Transmission) Input/Output: ± 0.2 % of Full Scale
  • Detected Current Accuracy: Setting ± 10 % of Full Scale
  • Input Indication: ± 0.1 % of Full Scale
  • Resistance Bulb Input: (± 0.1 % of Full Scale ± 1-Digit) or ± 0.25° C (0.45° F), whichever is Larger
  • Thermocouple B (0° to 400° C): ± 5 % of Full Scale ± 1-Digit ± 1° C (± 1.8° F)
  • Thermocouple R (0° to 500° C Range): ± 1 % of Full Scale ± 1-Digit ± 1° C ± 1° C (± 1.8° F)
  • Thermocouple: ± 0.1 % of Full Scale ± 1-Digit ± 1° C (± 1.8° F) or ± 1.5° C (± 2.7° F), whichever is Larger
  • Voltage, Current Input: ± 0.1 % of Full Scale ± 1-Digit

Ambient Temperature Range

  • -10° to 50° C (14° to 122° F)

Approvals & Certifications

  • CE Mark
  • UL, C-UL

Communication

  • Baud Rate: 9,600, 19,200, 38,400 bit/sec
  • Data Length: 8-bits, Parity, Odd / Even / None
  • Method: 3-Wire, Half-Duplex Bit Serial
  • Method: Asynchronous Communication
  • PC Loader Interface: RS-232C
  • Protocol: Modbus RTU
  • RS-485

Connectors

  • PC Loader Interface: Miniature Jack on Bottom Face

Consumption

  • Power Consumption: 15 VA or Less (100 Vac)
  • Power Consumption: 20 VA or Less (220 Vac)

Control Functions Characteristics

  • PID Control

Display

  • LED Display

Distance

  • RS-485 Communication Distance: 0 to 1,640 feet (0 to 500 metres)

Electrical Contacts

  • Normally Open

Electrical Rating

  • 3-Digital Input: 2 mA at 12 Vdc
  • Contact Capacity: 3 A at 30 Vdc
  • Cooling / Motorized Valve Operation Pulse Output: 0.3 A at 220 Vac / 30 Vdc
  • Relay Contact / Digital / Cooling / Motorized Valve Operation Pulse Output: 1 A at 220 Vac / 30 Vdc (Inductive Load)
  • Relay Contact: 3 A at 220 Vac / 30 Vdc - Resistive Load

Enclosure, Body Material

  • Plastic (Flame-Resistant, UL 94V-0)

Environmental Protection

  • Body: IEC IP20 (Provided with Slits on Top & Bottom Faces)
  • Front Face: IP66 (When Mounted on Panel with Our Genuine Packing. Waterproof Feature Unavailable in Side-by-Side Mounting)
  • Front Face: NEMA 4X (When Mounted on Panel with Our Genuine Packing. Waterproof Feature Unavailable in Side-by-Side Mounting)
  • Terminal Section: IEC IP00 (Terminal Cover Can be Mounted)

Filter

  • First Order Lag Filter: 0 to 900 seconds

Function

  • Alarm (Heater Burn-Out) Detectable Range: 1-50 A, Detected Current / Setting Resolution: 0.1 A

Humidity

  • Operating/Storage Ambient Humidity: 90 % Relative Humidity, Max.

Input

  • Current Input: -25 to 25 mA
  • DC Voltage Input: -10 to 35 V
  • Heater Current Detector (CT): 1-30 A
  • Heater Current Detector (CT): 20-50 A
  • Input Judgment: OFF Assumed at 100 kiloohms or Higher (Contact) or 18 Vdc or Higher (Transistor)
  • Input Judgment: ON Assumed at 1 Kiloohm or Lower (Contact) or 5 Vdc or Lower (Transistor)
  • Thermocouple, Resistance Bulb, mV Input: 0-10 Vdc
  • Thermocouple, Resistance Bulb, mV Input: 0-20 mVdc
  • Thermocouple, Resistance Bulb, mV Input: 0-5 mV
  • Thermocouple, Resistance Bulb, mV Input: 4-20 mA DC

Input Impedance

  • Process Value Input: 250 ohms
  • Thermocouple, mV, Voltage & Auxiliary Analog (Remote SV) Input: 1 Megaohm Min.

Input Signal

  • 0-50 mV
  • Auxiliary Analog Input (Remote SV Input): 0-5 Vdc

Insulation Resistance

  • 20 megaohms at 500 Vdc

Linearity

  • Current Output: ± 0.2 % of Full Scale

Load Resistance

  • SSR/SSC Drive Output: 850 ohms Min.
  • SSR / SSC Drive / Auxiliary Analog (Re-Transmission) Output (Current): 600 ohms or more or Less
  • SSR/SSC Drive/Auxiliary Analog (Re-Transmission) Output (Voltage): 10 kiloohms Min.

Mounting

  • Panel Flush Mounting

Operation

  • Contact Life (Output): 100,000 times or more (Rated Load)

Output

  • Auxiliary Analog (Re-Transmission) Output: 0-10 Vdc
  • Auxiliary Analog (Re-Transmission) Output: 0-20 mA
  • Auxiliary Analog (Re-Transmission) Output: 0-5 Vdc
  • Auxiliary Analog (Re-Transmission) Output: 1-5 Vdc
  • Auxiliary Analog (Re-Transmission) Output: 4-20 mA
  • SSR/SSC Drive Output (ON): 20 Vdc (18-24 Vdc)
  • Transmitter Power Supply Output: 23 mA
  • Transmitter Power Supply Output: 24 Vdc (17-30 Vdc)

Output Cycle

  • 200 milliseconds

Output Noise

  • Noise Rejection Ratio (Common Mode): 120 dB (50/60 Hz)
  • Noise Rejection Ratio (Normal Mode): 40 dB (50/60 Hz)

Power Supply

  • 100-240 Vac (-15 %, 10 %), 50/60 Hz

Resistance

  • Input: 250 ohms
  • Resistance Bulb: 10 ohms or Less (per Cable)
  • Valve Opening Feedback Signal (Potentiometer): 100 to 10,000 ohms, 3-Wire
  • Variation by Signal Source Resistance: Thermocouple, mV Input ± 0.3 % of Full Scale ± 1-Digit Per 100 ohms
  • Variation by Signal Source Resistance: Voltage Input ± 0.3 % of Full Scale ± 1-Digit Per 500 ohms

Resistance Effect

  • Auxiliary Analog Input: 0.2 % of Full Scale Per 500 ohms
  • Thermocouple, Voltage Input (mV): 0.1 % of Full Scale Per 100 ohms
  • Voltage Input (V): 0.1 % of Full Scale Per 500 ohms

Resolution

  • Resistance Bulb Input: 0.01° C
  • Valve Opening Feedback Signal (Potentiometer): ± 0.1 % of Full Scale

RTD Type

  • Resistance Bulb: Pt100 ohms (3-Wire)

Sample Rate

  • Auxiliary Analog Input: 100 milliseconds
  • Input Control Cycle: 50 milliseconds

Sensor, Probe Type

  • B Thermocouple
  • E Thermocouple
  • J Thermocouple
  • K Thermocouple
  • N Thermocouple
  • R Thermocouple
  • S Thermocouple
  • T Thermocouple

Span & Zero Adjustments

  • ± 50 % of Full Scale

Storage Temperature

  • -20° to 60° C (-4° to 140° F)

Supply Voltage

  • Withstand Voltage: 500 Vac for 1 Minute
  • Withstand Voltage: Power Source to All Terminals, Relay Contact Output to All Terminals 1,500 Vac for 1 Minute

Switch Type

  • Motorized Valve Operation Pulse / Cooling / Digital Output: SPDT
  • Relay Contact / Digital Output: SPDT

Temperature Range

  • -200° to 2,300° C (-328° to 4,172° F)

Terminal Strip